What should be noted in installation of the level gauge of guided wave radar?

Guided wave radar level gauge has the advantages of low maintenance, high performance, high precision, high reliability and long life. Compared with the contact instruments such as capacitance and weight, it has incomparable advantages. Microwave signal transmission is not affected by the atmosphere, and can meet the requirements of volatile gas, high temperature, high pressure, steam, vacuum and high dust in the process.

Guided wave radar level gauge is suitable for high temperature (350 ℃), high pressure, vacuum, steam, high dust, volatile gas and other harsh environment. It can continuously measure different material levels. The main technical indexes of the instrument are up to or better than those of similar products at home and abroad, and the installation and debugging are simple. It can be used in a single collection or in a network. Guided wave radar level gauge is used in metallurgy, building materials, energy, petrochemical, water conservancy, grain and other industries.

Precautions for installation of guided wave radar level gauge:

① The rod probe and cable probe should be far away from the feed port as far as possible to avoid abrasion;

② The rod probe and cable probe shall keep a certain distance from the tank wall and bottom, and shall not contact with the metal tank wall and bottom;

③ When the tank wall adheres, the distance between the probe and the tank wall should be at least 100 mm;

④ The end of the probe shall be at least 100 mm away from the tank wall and the small distance from the tank bottom: Cable probe (150 mm); Rod probe (50 mm); Coaxial rod probe (10 mm);

⑤ The installation of rod probe and cable probe shall keep a distance of more than 300 mm from the installed tuning fork bracket and other equipment to avoid interference;

⑥ Select the appropriate installation position to avoid the probe bending during installation or operation;

⑦ Before installation, the probe should be checked for damage, and the installation should be carried out in the empty warehouse;

⑧ It is recommended to use this sample shield for outdoor installation;

Company profile

安徽炫瑞自動(dòng)化控制系統(tǒng)有限公司-官網(wǎng)
Anhui xuanrui Automation Control System Co., Ltd. has developed, developed and produced more than 30 kinds of products, including tuning fork switch, RF admittance switch, electrode level switch, spin level switch, magnetic flap level gauge, magnetostrictive level gauge, floating ball level gauge......